TDR-240-24 meanwell TDR series Power Supply Din Rail Switching Power supply LED Driver tdr-240-24
Product Introduction
Features
Specification
MODEL |
TDR-240-24 |
TDR-240-48 |
|
OUTPUT |
DC VOLTAGE |
24V |
48V |
RATED CURRENT |
10A |
5A |
|
CURRENT RANGE |
0~10A |
0~5A |
|
RATED POWER |
240W |
240W |
|
RIPPLE & NOISE (max.) |
100mVp-p |
120mVp-p |
|
VOLTAGE ADJ. RANGE |
24~28V |
48~55V |
|
VOLTAGE TOLERANCE |
+1.0% |
士1.0% |
|
LINE REGULATION |
士0.5% |
士0.5% |
|
LOAD REGULATION |
士1.0% |
士1.0% |
|
SETUP, RISE TIME |
2000ms,60ms/400VAC 1500ms,60ms/500VAC at full load |
||
HOLD UP TIME (TyP.) |
20ms/400VAC 40ms/500VAC at full load |
||
INPUT |
VOLTAGE RANGE |
Three-Phase 340 ~ 550VAC (Dual phase operation possible in connecting L1,L3,FG or L2,L3,FG) or 480 ~ 780VDC |
|
FREQUENCY RANGE |
47~63Hz |
||
POWER FACTOR(Typ.) |
PF≥0.53/400VAC PF≥0.52/500VAC at full load |
||
EFFICIENCY (Typ.) |
92% |
92% |
|
AC CURRENT (TyP.) |
0.69A/400VAC 0.6AV/500VAC |
||
INRUSH CURRENT (TyP.) |
COLD START 50A |
||
LEAKAGE CURRENT |
<2mA/530VAC |
||
PROTECTION |
OVERLOAD |
105~130% rated output power |
|
Protection type : Constant current limiting, unit will hiccup after 3 sec. | |||
OVER VOLTAGE |
30~36V |
56~65V |
|
Protection type : Hiccup mode, recovers automatically after fault condition is removed. | |||
OVER TEMPERATURE |
Shut down o/p voltage, recovers automatically after temperature goes down |
||
ENVIRONMENT |
WORKING TEMP. |
-30~+70℃ (Refer to "Derating Curve") |
|
WORKING HUMIDITY |
20~95% RH non-condensing |
||
STORAGE TEMP., HUMIDITY |
-40~+85'℃,10~95% RH |
||
TEMP. COEFFICIENT |
+0.05%/℃ (0~60℃) |
||
VIBRATION |
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along x, Y, Z axes; Mounting: Compliance tolEC60068-2-6 |
||
OTHERS |
MTBF |
1534.9Khrs min. Telcordia SR-332 (Bellcore) : 215.6K hrs min.MIL-HDBK-217F(25°C) |
|
DIMENSION |
63*125.2*113.5mm(W*H*D) |
||
PACKING |
1Kg: 12pcs/13Kg/1.22CUFT |
||